How to change to T-506H intelligent temperature mode for CW-6100 chiller

Firstly, we should judge the type of temperature controller

This is T-506H temperature controller which works in defaulted constant temperature control mode
CHILLER
Now, we should change to intelligent temperature mode
Press and keep holding "â–³" and "SET"bottons for 5 seconds until "00" and "PAS" displayed
Press"â–³" botton to select the password(default setting is 8) and then press "SET"botton into setup status
Press ">"botton to turn to item F3 that means way of control, "0" means constant control, Press [â–³" to ajust to "1 " that means intelligent control,Press"RST"key to save the modification
Now the chiller is working in intelligent temperature mode, Thanks.
The video about temperature mode change: http://Article/Howtochangeintelli_1_1.html